| Problem | Possible Cause | Possible Solution |
|---|---|---|
| 5.0 No RDY or COM Light | (1) Bad power cable connection/damaged cable | (1) Inspect the drive power cables for damage. (2) Ensure that no breakers are flipped. |
| (2) Bad drive | (1) Contact Spire for a replacement. | |
| 5.1 Red COM Light | (1) Communications with the PLC were lost | (1) Check the ethernet cable between the drive units with the orange COM lights and the drive units with green COM lights. Replace if needed. (2) Power cycle the range if the problem continues. |
| 5.2 Flashing Red RDY Light | (1) Alarm/Fault Occurred | (1) See 5.3 and onward. |
| 5.3 Fault F1911 (PROFIdrive: Clock cycle synchronous operation clock cycle failure) | (1) Communications with the PLC were lost | (1) See 5.1. |
| 5.4 Fault F1912 (PROFIdrive: Clock cycle synchronous operation sign-of-life failure) | (1) Communications with the PLC were lost | (1) See 5.1. |
| 5.5 Fault F7011 (Motor overtemperature) | (1) Motor overheated | (1) Power down targets on touch screen. (2) Wait 15-30 min for motors to cool down. |
| 5.6 Fault F7450 (Standstill monitoring has responded) | (1) Clamp hitting shaft guard when spinning 360 | (1) Pull up on the target clamp to close the jaws on the target further. (2) If that does not solve the issue, file the shaft guard down slightly to remove the interference. |
| (2) Obstruction in belt | (1) Turn the targets off using the button on the touch screen. (2) Open the side of the motor housing (hogan house). (3) Remove any obstructions between the belt and the gears. | |
| (3) Belt too tight | (1) Open the side of the motor housing (hogan house). (2) Slightly loosen the button heads holding the motor bracket to the side of the hogan house. DO NOT remove completely. (3) Loosen the belt tensioning bolt (near the stand) slightly. It may be easier to remove the hogan house from the stand. Watch the cables for snagging. | |
| 5.7 Fault F7900 (Motor blocked/speed controller at its limit) | (1) Clamp hitting shaft guard when spinning 360 | (1) See 5.3. |
| (2) Obstruction in belt | (1) See 5.3. | |
| (3) Belt too tight | (1) See 5.3. | |
| 5.8 Fault F8501 (PROFIdrive: Setpoint timeout) | (1) Communications with the PLC were lost | (1) See 5.1. |
| 5.9 Fault F30004 (Drive heat sink overtemperature) | (1) Drive overheated | (1) Power down targets on touch screen. (2) Wait 15-30 min for motors to cool down. (3) If problem persists, check that the drive fans are running and not blocked. |
| 5.10 Fault F30011 (Line phase failure in main circuit) | (1) Power cable damaged/loose | (1) Power down main breaker. (2) Check all power wiring (208VAC when live). |
| (2) Motor phase failed | (1) Power down main breaker. (2) Check good connection on the orange motor power cable. (3) If problem persists, replace orange motor power cable while powered off. (4) If problem persists, replace target motor while powered off. | |
| 5.11 Fault F30015 (Phase failure motor cable) | (1) Motor phase failed | (1) See 5.10.2. |
| 5.12 Fault F30021 (Ground Fault) | (1) Ground fault detected | (1) See 5.10. |
| 5.13 Fault F30036 (Internal overtemperature) | (1) Drive overheated | (1) See 5.9. |
| 5.14 Fault F31111 (Encoder 1: Absolute encoder internal error) | (1) Motor overheated | (1) See 5.5. |
| (2) Encoder not detected | (1) Power down main breaker. (2) Check good connection on the green motor cable. (3) If problem persists, replace green motor cable while powered off. (4) If problem persists, replace target motor while powered off. | |
| 5.15 Fault F52983 (No encoder detected) | (1) Encoder not detected | (1) See 5.14.2. |
| 5.16 Alarm A1009 (Control module overtemperature) | (1) Drive overheated | (1) See 5.9. |
| 5.17 Alarm A5000 (Drive heat sink overtemperature) | (1) Drive overheated | (1) See 5.9. |
| 5.18 Alarm A8526 (PROFIdrive: No cyclic connection) | (1) Communications with the PLC were lost | (1) See 5.1. |